⚠ Important — NEC code adoption timelines vary significantly by state and municipality. Some jurisdictions are on NEC 2017 or 2020. The requirements below reflect NEC 2023. Always confirm which NEC edition your local AHJ has adopted before roughing in. This information is for general reference only and is not electrical advice.

GFCI & AFCI Requirements by Location

Location GFCI Required AFCI Required Code Reference Notes
Bathrooms YES NO NEC 210.8(A)(1) All receptacles within bathrooms, regardless of distance from water
Garages YES NO NEC 210.8(A)(2) All 125V, 15A and 20A receptacles; includes attached/detached garages
Outdoors YES NO NEC 210.8(A)(3) All outdoor receptacles at grade level and accessible to unfinished spaces
Crawl spaces YES NO NEC 210.8(A)(4) At or below grade level
Unfinished basements YES NO NEC 210.8(A)(5) Not required for dedicated appliance receptacles or fire alarm circuits
Kitchen countertops YES YES NEC 210.8(A)(6) Within 6 ft of sink edge; all countertop receptacles
Within 6 ft of sink (non-kitchen) YES NO NEC 210.8(A)(7) Laundry, utility, wet bar sinks
Boathouses YES NO NEC 210.8(A)(8) All receptacles
Bathtubs/shower stalls (within 6 ft) YES NO NEC 210.8(A)(9) Even if not in a bathroom by definition
Laundry areas YES YES NEC 210.8(A)(10) Added in 2023 NEC; verify local adoption
Bedrooms NO YES NEC 210.12 AFCI required for all 120V, 15A and 20A bedroom circuits
Living/family rooms NO YES NEC 210.12 AFCI required in 2020+ NEC; verify local adoption
Hallways/closets NO YES NEC 210.12 AFCI required in 2020+ NEC; verify local adoption
YES GFCI required — protects against shock from ground faults
YES AFCI required — protects against fires from arc faults
NO Not required by 2023 NEC (local code may differ)

Breaker Size & Wire Gauge Quick Reference

Breaker Size Minimum Wire Gauge Typical Applications
15A 14 AWG Lighting circuits, small appliances, general outlets
20A 12 AWG Kitchen outlets, bathroom outlets, laundry, garage
30A 10 AWG Electric dryers, water heaters, AC units, welders
40A 8 AWG Electric ranges, large AC units
50A 8 AWG (AL) or 6 AWG (CU) Electric ranges, EV chargers (Level 2), large spas
60A 6 AWG Subpanels, large HVAC, EV chargers
100A 2 AWG (CU) or 1/0 AWG (AL) Small subpanels, large outbuildings
150A 1/0 AWG (CU) or 2/0 AWG (AL) Medium subpanels, service entrance
200A 3/0 AWG (CU) or 4/0 AWG (AL) Main residential service entrance, large subpanels
GFCI vs. AFCI: What's the Difference?

GFCI (ground-fault) protection detects current leaking to ground — typically a shock hazard near water. AFCI (arc-fault) protection detects the electrical signature of arcing — typically a fire hazard from damaged wiring. They protect against different failure modes.

Combination AFCI Breakers

Combination-type AFCI breakers (CAFCI) provide both series and parallel arc-fault protection and are required by NEC 2014+. Standard AFCI breakers are no longer code-compliant for new installations.

GFCI Device vs. GFCI Breaker

You can provide GFCI protection either with a GFCI outlet at the first receptacle in a circuit (protecting all downstream outlets) or with a GFCI breaker at the panel. Both are NEC-compliant. GFCI outlets are cheaper; breakers protect the entire circuit including the wire run.

Sources: NEC 2023 Articles 210.8 and 210.12 · NFPA 70 Data reviewed Q1 2026 — verify adopted NEC edition with your local AHJ