⚠ Important — Ampacity values depend on conduit fill, ambient temperature, insulation type, bundling, and installation method. Values shown are general reference only and do not account for derating factors. Always calculate final ampacity per NEC Article 310 and verify with a licensed electrician or your local AHJ. This is not electrical advice.

AWG Ampacity Table — Copper Conductors

AWG Diameter (in) Area (cmil) Resistance (Ω/kft) Max Amps (chassis) Max Amps (power trans.) Common Uses
AWG 14 0.0641" 4,110 2.525 32A 11A General household wiring, 15A circuits, lighting
AWG 12 0.0808" 6,530 1.588 41A 16A 20A circuits, kitchen outlets, bathrooms, GFCI circuits
AWG 10 0.1019" 10,380 0.9989 55A 22A Dryers, water heaters, AC units (30A circuits)
AWG 8 0.1285" 16,510 0.6282 73A 32A Electric ranges, large AC units, subpanels (40A-50A)
AWG 6 0.162" 26,250 0.3951 101A 47A Subpanels, EV chargers, large appliances (55A-60A)
AWG 4 0.2043" 41,740 0.2485 135A 67A Service entrance, large subpanels (70A-85A)
AWG 2 0.2576" 66,360 0.1563 181A 95A Service entrance conductors, large feeders (95A-100A)
AWG 1/0 0.3249" 105,600 0.09827 245A 150A Main service entrance, large feeders (125A-150A)
AWG 2/0 0.3648" 133,100 0.07793 283A 175A Main service entrance (150A-175A)
AWG 3/0 0.4096" 167,800 0.0618 328A 200A Main service entrance (200A residential)
AWG 4/0 0.46" 211,600 0.04901 380A 230A Large commercial service, main feeders (230A+)
Remember: Bigger AWG = Thinner Wire

AWG (American Wire Gauge) is counterintuitive. A lower gauge number means a thicker, higher-capacity wire. 10 AWG is thicker than 14 AWG.

Aluminum vs. Copper

Aluminum conductors require approximately 1 AWG size larger for equivalent ampacity. Use only AL-rated connectors and terminals. Anti-oxidant compound required.

Derating Rules (NEC 310.15)

More than 3 current-carrying conductors in a raceway requires derating. At 4-6 conductors: 80%. At 7-9: 70%. At 10-20: 50%. Always apply derating before selecting wire size.

Common Insulation Types

Type Temp Rating Voltage Typical Use
THHN/THWN 90°C dry / 75°C wet 600V Most common building wire; conduit applications, dry/wet locations
NM-B (Romex) 90°C (60°C in conduit) 600V Residential interior wiring; NOT for conduit, wet, or outdoor use
UF-B 60°C 600V Underground feeder; direct burial, outdoor, wet locations
XHHW-2 90°C dry and wet 600V High heat and moisture resistance; commercial/industrial
USE-2/RHH/RHW-2 90°C 600V Solar PV wiring, underground service entrance
Sources: NEC 2023 Table 310.12 · NEC Article 310 · NFPA 70 Data reviewed Q1 2026 — verify with current NEC edition and local AHJ